Wednesday, April 28, 2010

Vacuum Condensers


Outlet Temperature and Pressure. It is important to have proper subcooling in the vent end of the unit to prevent large amounts of process vapors from going to the vacuum system along with the inerts.

Control. It is necessary to have some over-surface and to have a proper baffling to allow for pressure control during process swings, variable leakage of inerts, etc. One designer adds 50% to the calculated length for the oversurface. The condenser must be considered part of the control system (similar to extra trays in a fractionator to allow for process swings not controlled by conventional instrumentation).


The inerts will “blanket” a portion of the tubes. The blanketed portion has very poor heat transfer. The column pressure is controlled by varying the percentage of the tube surface blanketed. When the desired pressure is exceeded, the vacuum system will suck out more inerts, and lower the percentage of surface blanketed. This will increase cooling and bring the pressure back down to the desired level. The reverse happens if the pressure falls below that desired. This is simply a matter of adjusting the heat transfer coefficient to heat balance the system.

Figure 1 shows typical baffling. The inerts move through the first part of the condenser as directed by the baffles. The inerts then pile up at the outlet end lowering heat transfer as required by the controller. A relatively large section must be covered by more or less stagnant inerts which are sub-cooled before being pulled out as needed. Without proper baffles, the inerts build up in the condensing section and decrease heat transfer until the pressure gets too high. Then the vacuum valve opens wider, pulling process vapor and inerts into the vacuum system. Under these conditions pressure control will be very poor.

Pressure Drop. Baffling must be designed to keep the pressure drop as low as possible. The higher the pressure drop the higher the energy consumption and the harder the job of attaining proper vent end sub-cooling. Pressure drop is lower at the outlet end because of smaller mass flow.

Bypassing. Baffles should prevent bypass of inlet vapor into the vent. This is very important.

Typical Condenser. Figure 1 illustrates an inlet “bathtub” used for low vacuums to limit pressure drop at entrance to exchanger and across first rows of tubes. Note staggered baffle spacing with large spacing at inlet, and the side to side (40% cut) baffles. Enough baffles must be used in the inlet end for minimum tube support. In the last 25% of the outlet end a spacing of 1/10 of a diameter is recommended.


Source: Based on notes provided by Jack Hailer and consultation by Guy Z. Moore while employed at El Paso Products Co.

2 comments:

  1. kok saya ga isa nulis di shoutmixnya ya?? keterangannya: "sorry, no name correct"
    itu kenapa ya??

    ReplyDelete
  2. www.vinithbejugamchemicalengineering.blogspot.com

    ReplyDelete